The Hargassner Magno series for industrial heating, can also be combined as a highly efficient cascade solution. In this industrial segment, highest heating outputs of up to 10 MW in series can be achieved. The sophisticated, well thought-out and constantly optimised Hargassner heating technology also stands for maximum reliability and high-quality workmanship in the industrial sector. In times of energy transition and rising prices for oil and gas, these industrial cascades are an optimal solution to save operating costs quickly and in the long term.

  • Heat output for highest industrial demands
  • Best operational reliability
  • Sophisticated control system tailored to your needs
  • High discharge volume
  • Sophisticated technology at the cutting edge
  • Hargassner Industry expert team for project planning & execution

Technical
details

Nominal Load [NL]
Fuel heat output
Minimum Load [ML]
Electrical consumption
NCV efficiency at nominal output
NCV efficiency at 30 % nominal output
GCV efficiency at nominal output
GCV at 30 % nominal output
Seasonal energy efficiency ETAs
Boiler temperature range
Dimensions (w x h x d)
Weight
Filling volume
Space requirement
Flue pipe diameter
Ash box volume
Water content
Flow/Return
Energy label
Unit
kW
kW
kW
kW
%
%
%
%
%
°C
mm
kg
l
mm
l
l
"
    Magno-UF 250
    Nominal Load [NL] 250 kW
    Fuel heat output 264,3 kW
    Minimum Load [ML] 75 kW
    Electrical consumption - kW
    NCV efficiency at nominal output in % 94,6 %
    NCV efficiency at 30 % nominal output in % - %
    GCV efficiency at nominal output - %
    GCV at 30 % nominal output - %
    Seasonal energy efficiency ETAs - %
    Boiler temperature range 95 °C
    Dimensions (w x h x d) 1160 x 2250 x 3160 mm
    Weight 4250 kg
    Filling volume - l
    Space requirement 3,67
    Flue pipe diameter 200 mm
    Ash box volume 240 / 800* l
    Water content 830 l
    Flow/Return 80/65 PN16 "
    Energy label -
    Magno-UF 300
    Nominal Load [NL] 280 kW
    Fuel heat output 297,9 kW
    Minimum Load [ML] 90 kW
    Electrical consumption - kW
    NCV efficiency at nominal output in % 94,0 %
    NCV efficiency at 30 % nominal output in % - %
    GCV efficiency at nominal output - %
    GCV at 30 % nominal output - %
    Seasonal energy efficiency ETAs - %
    Boiler temperature range 95 °C
    Dimensions (w x h x d) 1160 x 2250 x 3160 mm
    Weight 4250 kg
    Filling volume - l
    Space requirement 3,67
    Flue pipe diameter 200 mm
    Ash box volume 240 / 800* l
    Water content 830 l
    Flow/Return 80/80 PN16 "
    Energy label -
    Magno-UF 350
    Nominal Load [NL] 300 kW
    Fuel heat output 319,8 kW
    Minimum Load [ML] 105 kW
    Electrical consumption - kW
    NCV efficiency at nominal output in % 93,8 %
    NCV efficiency at 30 % nominal output in % - %
    GCV efficiency at nominal output - %
    GCV at 30 % nominal output - %
    Seasonal energy efficiency ETAs - %
    Boiler temperature range 95 °C
    Dimensions (w x h x d) 1260 x 2300 x 3350 mm
    Weight 5200 kg
    Filling volume - l
    Space requirement 4,22
    Flue pipe diameter 250 mm
    Ash box volume 240 / 800* l
    Water content 1100 l
    Flow/Return 80/80 PN16 "
    Energy label -
    Magno-UF 500
    Nominal Load [NL] 501 kW
    Fuel heat output 533 kW
    Minimum Load [ML] 150 kW
    Electrical consumption - kW
    NCV efficiency at nominal output in % 94 %
    NCV efficiency at 30 % nominal output in % - %
    GCV efficiency at nominal output - %
    GCV at 30 % nominal output - %
    Seasonal energy efficiency ETAs - %
    Boiler temperature range 95 °C
    Dimensions (w x h x d) 1460 x 2510 x 3875 mm
    Weight 6830 kg
    Filling volume - l
    Space requirement 5,66
    Flue pipe diameter 250 mm
    Ash box volume 240 / 800* l
    Water content 1550 l
    Flow/Return 100/100 PN 16 "
    Energy label -
    Magno-UF 550
    Nominal Load [NL] 550 kW
    Fuel heat output 587,6 kW
    Minimum Load [ML] 165 kW
    Electrical consumption - kW
    NCV efficiency at nominal output in % 93,6 %
    NCV efficiency at 30 % nominal output in % - %
    GCV efficiency at nominal output - %
    GCV at 30 % nominal output - %
    Seasonal energy efficiency ETAs - %
    Boiler temperature range 95 °C
    Dimensions (w x h x d) 1460 x 2510 x 3875 mm
    Weight 6830 kg
    Filling volume - l
    Space requirement 5,66
    Flue pipe diameter 250 mm
    Ash box volume 240 / 800* l
    Water content 1550 l
    Flow/Return 100/100 PN16 "
    Energy label -
    Magno-VR 250
    Nominal Load [NL] 250 kW
    Fuel heat output 266,5 kW
    Minimum Load [ML] 75 kW
    Electrical consumption - kW
    NCV efficiency at nominal output in % 93,8 %
    NCV efficiency at 30 % nominal output in % - %
    GCV efficiency at nominal output - %
    GCV at 30 % nominal output - %
    Seasonal energy efficiency ETAs 78 %
    Boiler temperature range - °C
    Dimensions (w x h x d) 1160 x 2610 x 3160 mm
    Weight 5100 kg
    Filling volume - l
    Space requirement 3,67
    Flue pipe diameter 200 mm
    Ash box volume 240 / 800* l
    Water content 830 l
    Flow/Return 80/65 PN16 "
    Energy label -
    Magno-VR 300
    Nominal Load [NL] 300 kW
    Fuel heat output 318,1 kW
    Minimum Load [ML] 90 kW
    Electrical consumption - kW
    NCV efficiency at nominal output in % 94,3 %
    NCV efficiency at 30 % nominal output in % - %
    GCV efficiency at nominal output - %
    GCV at 30 % nominal output - %
    Seasonal energy efficiency ETAs 79 %
    Boiler temperature range - °C
    Dimensions (w x h x d) 1160 x 2610 x 3160 mm
    Weight 5100 kg
    Filling volume - l
    Space requirement 3,67
    Flue pipe diameter 200 mm
    Ash box volume 240 / 800* l
    Water content 830 l
    Flow/Return 80/65 PN16 "
    Energy label -
    Magno-VR 350
    Nominal Load [NL] 350 kW
    Fuel heat output 369,2 kW
    Minimum Load [ML] 105 kW
    Electrical consumption - kW
    NCV efficiency at nominal output in % 94,8 %
    NCV efficiency at 30 % nominal output in % - %
    GCV efficiency at nominal output - %
    GCV at 30 % nominal output - %
    Seasonal energy efficiency ETAs 80 %
    Boiler temperature range - °C
    Dimensions (w x h x d) 1260 x 2650 x 3350 mm
    Weight 6025 kg
    Filling volume - l
    Space requirement 4,22
    Flue pipe diameter 250 mm
    Ash box volume 240 / 800* l
    Water content 1100 l
    Flow/Return 80/80 PN16 "
    Energy label -
    Magno-VR 395
    Nominal Load [NL] 390 kW
    Fuel heat output 409,7 kW
    Minimum Load [ML] 120 kW
    Electrical consumption - kW
    NCV efficiency at nominal output in % 95,2 %
    NCV efficiency at 30 % nominal output in % - %
    GCV efficiency at nominal output - %
    GCV at 30 % nominal output - %
    Seasonal energy efficiency ETAs 79 %
    Boiler temperature range - °C
    Dimensions (w x h x d) 1260 x 2650 x 3350 mm
    Weight 6025 kg
    Filling volume - l
    Space requirement 4,22
    Flue pipe diameter 250 mm
    Ash box volume 240 / 800* l
    Water content 1100 l
    Flow/Return 80/80 PN16 "
    Energy label -
    Magno-VR 399
    Nominal Load [NL] 399 kW
    Fuel heat output 419,1 kW
    Minimum Load [ML] 135 kW
    Electrical consumption - kW
    NCV efficiency at nominal output in % 95,2 %
    NCV efficiency at 30 % nominal output in % - %
    GCV efficiency at nominal output - %
    GCV at 30 % nominal output - %
    Seasonal energy efficiency ETAs 80 %
    Boiler temperature range - °C
    Dimensions (w x h x d) 1460 x 2950 x 3875 mm
    Weight 8540 kg
    Filling volume - l
    Space requirement 5,66
    Flue pipe diameter 250 mm
    Ash box volume 240 / 800* l
    Water content 1550 l
    Flow/Return 100/100 PN16 "
    Energy label -
    Magno-VR 450
    Nominal Load [NL] 450 kW
    Fuel heat output 470,2 kW
    Minimum Load [ML] 135 kW
    Electrical consumption - kW
    NCV efficiency at nominal output in % 95,7 %
    NCV efficiency at 30 % nominal output in % - %
    GCV efficiency at nominal output - %
    GCV at 30 % nominal output - %
    Seasonal energy efficiency ETAs 79 %
    Boiler temperature range - °C
    Dimensions (w x h x d) 1460 x 2950 x 3875 mm
    Weight 8540 kg
    Filling volume - l
    Space requirement 5,66
    Flue pipe diameter 250 mm
    Ash box volume 240 / 800* l
    Water content 1550 l
    Flow/Return 100/100 PN16 "
    Energy label
    Magno-VR 500
    Nominal Load [NL] 499 kW
    Fuel heat output 523,1 kW
    Minimum Load [ML] 150 kW
    Electrical consumption - kW
    NCV efficiency at nominal output in % 95,4 %
    NCV efficiency at 30 % nominal output in % - %
    GCV efficiency at nominal output - %
    GCV at 30 % nominal output - %
    Seasonal energy efficiency ETAs 79 %
    Boiler temperature range - °C
    Dimensions (w x h x d) 1460 x 2950 x 3875 mm
    Weight 8540 kg
    Filling volume - l
    Space requirement 5,66
    Flue pipe diameter 250 mm
    Ash box volume 240 / 800* l
    Water content 1550 l
    Flow/Return 100/100 PN16 "
    Energy label -
    Magno-VR 550
    Nominal Load [NL] 535 kW
    Fuel heat output 560,8 kW
    Minimum Load [ML] 165 kW
    Electrical consumption - kW
    NCV efficiency at nominal output in % 95,4 %
    NCV efficiency at 30 % nominal output in % - %
    GCV efficiency at nominal output - %
    GCV at 30 % nominal output - %
    Seasonal energy efficiency ETAs 79 %
    Boiler temperature range - °C
    Dimensions (w x h x d) 1460 x 2950 x 3875 mm
    Weight 8540 kg
    Filling volume - l
    Space requirement 5,66
    Flue pipe diameter 350 mm
    Ash box volume 240 / 800* l
    Water content 1550 l
    Flow/Return 100/100 PN16 "
    Energy label -
    Magno-VR 600
    Nominal Load [NL] 550 kW
    Fuel heat output 582,6 kW
    Minimum Load [ML] 180 kW
    Electrical consumption - kW
    NCV efficiency at nominal output in % 94,40 %
    NCV efficiency at 30 % nominal output in % - %
    GCV efficiency at nominal output - %
    GCV at 30 % nominal output - %
    Seasonal energy efficiency ETAs 79 %
    Boiler temperature range - °C
    Dimensions (w x h x d) 1460 x 2950 x 3875 mm
    Weight 8540 kg
    Filling volume - l
    Space requirement 5,66
    Flue pipe diameter 350 mm
    Ash box volume 240 / 800* l
    Water content 1550 l
    Flow/Return 100/100 PN16 "
    Energy label -
    Magno-SR 800
    Nominal Load [NL] 850 kW
    Fuel heat output 888,2 kW
    Minimum Load [ML] 240 kW
    Electrical consumption - kW
    NCV efficiency at nominal output in % 95,7 %
    NCV efficiency at 30 % nominal output in % - %
    GCV efficiency at nominal output - %
    GCV at 30 % nominal output - %
    Seasonal energy efficiency ETAs 81 %
    Boiler temperature range - °C
    Dimensions (w x h x d) 1750 x 3700 x 5000 mm
    Weight 18000 kg
    Filling volume - l
    Space requirement 8,75
    Flue pipe diameter 400 mm
    Ash box volume 240 / 800* l
    Water content 2800 l
    Flow/Return 125/125 PN16 "
    Energy label -
    Magno-SR 995
    Nominal Load [NL] 995 kW
    Fuel heat output 1041,9 kW
    Minimum Load [ML] 299 kW
    Electrical consumption - kW
    NCV efficiency at nominal output in % 95,5 %
    NCV efficiency at 30 % nominal output in % - %
    GCV efficiency at nominal output - %
    GCV at 30 % nominal output - %
    Seasonal energy efficiency ETAs 81 %
    Boiler temperature range - °C
    Dimensions (w x h x d) 1750 x 3700 x 5000 mm
    Weight 18000 kg
    Filling volume - l
    Space requirement 8,75
    Flue pipe diameter 400 mm
    Ash box volume 240 / 800* l
    Water content 2800 l
    Flow/Return 125/125 PN16 "
    Energy label -
    Magno-SR 998
    Nominal Load [NL] 900 kW
    Fuel heat output 942,4 kW
    Minimum Load [ML] 300 kW
    Electrical consumption - kW
    NCV efficiency at nominal output in % 95,5 %
    NCV efficiency at 30 % nominal output in % - %
    GCV efficiency at nominal output - %
    GCV at 30 % nominal output - %
    Seasonal energy efficiency ETAs - %
    Boiler temperature range - °C
    Dimensions (w x h x d) 1950 x 3980 x 5070 mm
    Weight 21400 kg
    Filling volume - l
    Space requirement 9,88
    Flue pipe diameter 400 mm
    Ash box volume 240 / 800* l
    Water content 3500 l
    Flow/Return 125/125 PN16 "
    Energy label -
    Magno-SR 999
    Nominal Load [NL] 999 kW
    Fuel heat output 1046,1 kW
    Minimum Load [ML] 300 kW
    Electrical consumption - kW
    NCV efficiency at nominal output in % 95,5 %
    NCV efficiency at 30 % nominal output in % - %
    GCV efficiency at nominal output - %
    GCV at 30 % nominal output - %
    Seasonal energy efficiency ETAs - %
    Boiler temperature range - °C
    Dimensions (w x h x d) 1950 x 3980 x 5070 mm
    Weight 21400 kg
    Filling volume - l
    Space requirement 9,88
    Flue pipe diameter 400 mm
    Ash box volume 240 / 800* l
    Water content 3500 l
    Flow/Return 125/125 PN16 "
    Energy label -
    Magno-SR 1200
    Nominal Load [NL] 1200 kW
    Fuel heat output 1260,5 kW
    Minimum Load [ML] 360 kW
    Electrical consumption - kW
    NCV efficiency at nominal output in % 95,2 %
    NCV efficiency at 30 % nominal output in % - %
    GCV efficiency at nominal output - %
    GCV at 30 % nominal output - %
    Seasonal energy efficiency ETAs 80 %
    Boiler temperature range - °C
    Dimensions (w x h x d) 1750 x 3700 x 5000 mm
    Weight 18000 kg
    Filling volume - l
    Space requirement 8,75
    Flue pipe diameter 400 mm
    Ash box volume 240 / 800* l
    Water content 2800 l
    Flow/Return 125/125 PN16 "
    Energy label -
    Magno-SR 1400
    Nominal Load [NL] 1400 kW
    Fuel heat output 1497,3 kW
    Minimum Load [ML] 420 kW
    Electrical consumption - kW
    NCV efficiency at nominal output in % 93,5 %
    NCV efficiency at 30 % nominal output in % - %
    GCV efficiency at nominal output - %
    GCV at 30 % nominal output - %
    Seasonal energy efficiency ETAs - %
    Boiler temperature range - °C
    Dimensions (w x h x d) 1950 x 3980 x 5070 mm
    Weight 21400 kg
    Filling volume - l
    Space requirement 9,88
    Flue pipe diameter 400 mm
    Ash box volume 240 / 800* l
    Water content 3500 l
    Flow/Return 125/125 PN16 "
    Energy label -
    Magno-SR 2000
    Nominal Load [NL] 2000 kW
    Fuel heat output 2128,3 kW
    Minimum Load [ML] 600 kW
    Electrical consumption - kW
    NCV efficiency at nominal output in % 93,5 %
    NCV efficiency at 30 % nominal output in % - %
    GCV efficiency at nominal output - %
    GCV at 30 % nominal output - %
    Seasonal energy efficiency ETAs - %
    Boiler temperature range - °C
    Dimensions (w x h x d) 1950 x 3980 x 6700 mm
    Weight 28500 kg
    Filling volume - l
    Space requirement 13,07
    Flue pipe diameter 500 mm
    Ash box volume 240 / 800* l
    Water content 5100 l
    Flow/Return 200/200 PN16 "
    Energy label -
    Magno-SR 2400
    Nominal Load [NL] 2250 kW
    Fuel heat output 2406,4 kW
    Minimum Load [ML] 675 kW
    Electrical consumption - kW
    NCV efficiency at nominal output in % 93,5 %
    NCV efficiency at 30 % nominal output in % - %
    GCV efficiency at nominal output - %
    GCV at 30 % nominal output - %
    Seasonal energy efficiency ETAs - %
    Boiler temperature range - °C
    Dimensions (w x h x d) 1950 x 3980 x 6700 mm
    Weight 28500 kg
    Filling volume - l
    Space requirement 13,07
    Flue pipe diameter 500 mm
    Ash box volume 240 / 800* l
    Water content 5100 l
    Flow/Return 200/200 PN16 "
    Energy label -
    Magno-SR 2500
    Nominal Load [NL] 2500 kW
    Fuel heat output 2663,1 kW
    Minimum Load [ML] 750 kW
    Electrical consumption - kW
    NCV efficiency at nominal output in % 93,5 %
    NCV efficiency at 30 % nominal output in % - %
    GCV efficiency at nominal output - %
    GCV at 30 % nominal output - %
    Seasonal energy efficiency ETAs - %
    Boiler temperature range - °C
    Dimensions (w x h x d) 1950 x 3980 x 6700 mm
    Weight 28500 kg
    Filling volume - l
    Space requirement 13,07
    Flue pipe diameter 500 mm
    Ash box volume 240 / 800* l
    Water content 5100 l
    Flow/Return 200/200 PN16 "
    Energy label -

    NCV = Net Calorific Value | GCV = Gross Calorific Value
    per cascade boiler:
    max. operation temperature 95 °C | max. operating pressure 6 bar | electrical supply 400 V AC, 50 Hz, 25 A fuse protection

    Target group
    & possible areas of application

    The right boiler for every power requirement.

    Your new heating system
    in just a few steps

    More about Hargassner

    01

    Contact us

    Contact us for get some more
    information and make an appointment!

    02

    Request

    Our team looks forward to
    hearing from you and providing
    you with professional advice.

    03

    Appoint­ment

    We will inform you in detail
    about our heating systems and the
    corresponding heating supplies
    for your biomass heating system.

    04

    Offer

    We create an energy- and
    cost-efficient offer that
    is tailored to your needs.

    In your region

    Contact us
    for individual

    consultation

    Contact us